Skip to main content
Sign in Register
Question no. 28159

When does negative phase sequence occur in a 3-phase synchronous motor_______________?

Select your answer for: When does negative phase sequence occur in a 3-phase synchronous motor_______________?
Show answer

Answer: A. supplied with unbalanced voltage

Explanation

Negative phase sequence currents appear in a synchronous motor when supply voltages are unbalanced. Unbalanced three-phase supply voltages contain symmetrical components including negative sequence voltages. Negative sequence voltages drive reverse-rotating magnetic fields that induce double-frequency currents in the rotor. Symmetrical components theory breaks unbalanced polyphase systems into positive, negative, and zero sequences. A perfectly balanced three-phase supply generates only positive sequence magnetic rotating fields. Negative sequence fields rotate in the opposite direction to the normal mechanical rotor rotation.

Power system faults like single-phase short circuits create severe voltage unbalance across motor terminals. Negative phase sequence currents cause rapid localized overheating in rotor damping and field windings. Protection engineers install phase unbalance relays to trip motors before thermal damage occurs. Under-loaded operating conditions affect current magnitude but do not introduce negative phase sequences. Over-loaded conditions increase positive sequence armature current without creating negative sequence voltages. Stating none of the above is incorrect because supply voltage unbalance is the exact cause.

Subject
Engineering
Topic
—
Difficulty
medium

Related questions

Q1. Where are damper windings installed on a synchronous motor____________?

Select your answer for: Where are damper windings installed on a synchronous motor____________?
Show answer

Answer: C. pole faces

Damper windings are embedded directly into the pole faces of a synchronous motor rotor. These copper or brass bars run parallel to the rotor shaft along the magnetic poles. Embedding them in the pole faces ensures close...

Q2. For power factor correction purposes, synchronous motors are run at____________?

Select your answer for: For power factor correction purposes, synchronous motors are run at____________?
Show answer

Answer: A. no-load and greatly over-excited fields

Running the synchronous motor at no-load eliminates the need to consume real mechanical shaft power. Greatly over-exciting the rotor fields maximizes the leading reactive power generated by the machine. This specific ope...

Q3. Sudden open-circuiting of the field circuit in an unloaded salient-pole synchronous motor causes

Select your answer for: Sudden open-circuiting of the field circuit in an unloaded salient-pole synchronous motor causes
Show answer

Answer: B. the motor stops

Open-circuiting the field winding of an unloaded salient-pole synchronous motor destroys its excitation. Loss of field excitation eliminates the magnetic locking force between rotor and stator poles. Without synchronous...

Q4. The maximum power output of a synchronous motor depends on all factors except:

Select your answer for: The maximum power output of a synchronous motor depends on all factors except:
Show answer

Answer: C. direction of rotation

The maximum power output of a synchronous motor depends on rotor excitation, supply voltage, and load angle. Torque and power equations rely on the product of terminal voltage and excitation voltage magnitudes. The physi...

Q5. When does a synchronous motor draw high armature current____________?

Select your answer for: When does a synchronous motor draw high armature current____________?
Show answer

Answer: C. both high and low excitation

Very low excitation creates a weak magnetic field resulting in a large lagging armature current. Very high excitation creates a strong magnetic field resulting in a large leading armature current. Both extreme excitation...

Q6. What is the primary purpose of damping windings in synchronous motors______________?

Select your answer for: What is the primary purpose of damping windings in synchronous motors______________?
Show answer

Answer: D. prevent hunting and provide the starting torque

Damper windings serve to damp out rotor oscillations and provide asynchronous starting torque. Oscillations known as hunting are suppressed by eddy currents induced in the damper bars. During startup, the damper bars act...