Question no. 13301

Water flows and heats across a series of four tanks as illustrated. To design a cascade control system for regulating the exit temperature of tank 4 amidst disturbances in a secondary stream entering tank 2, where is the optimal location for the secondary loop measurement?

Select your answer for: Water flows and heats across a series of four tanks as illustrated. To design a cascade control system for regulating the exit temperature of tank 4 amidst disturbances in a secondary stream entering tank 2, where is the optimal location for the secondary loop measurement?
Show answer

Answer: C. Tank 3

Explanation

In cascade control schemes, the secondary measurement loop must be positioned close to the primary disturbance source. Placing the secondary sensor in tank 3 intercepts upstream thermal disturbances before they severely impact tank 4. This configuration allows the secondary controller to take rapid corrective action long before the upset reaches the final exit. Cascade control utilizes a secondary inner control loop to improve control performance against intermediate process disturbances. Multi-tank fluid systems exhibit distributed thermal capacitances that transmit temperature upsets sequentially from tank to tank. Upstream secondary measurements significantly reduce the effective time constant experienced by the primary control loop.

Tank 1 is located too far upstream, making its measurement insensitive to disturbances entering specifically through the secondary stream. Measuring in tank 2 places the secondary loop directly at the disturbance source, but tank 3 provides a better intermediate cascade balance. Tank 4 serves as the primary controlled variable location, which must remain at the outer master controller output.

Subject
Engineering
Topic
—
Difficulty
medium

Related questions

Q1. The transfer function representing a transportation lag is___________________?

Select your answer for: The transfer function representing a transportation lag is___________________?
Show answer

Answer: B. e-TS

The Laplace transform of a pure transportation lag or dead time of duration T is expressed as e^-TS. Applying this exponential term shifts the time domain signal forward by exactly T units without altering its shape. Fre...

Q2. Ultra-low pressures are denoted in microns (μ), equivalent to ____________ mm of Hg column (absolute) at 0°C?

Select your answer for: Ultra-low pressures are denoted in microns (μ), equivalent to ____________ mm of Hg column (absolute) at 0°C?
Show answer

Answer: B. 0.001

One micron of mercury pressure represents an ultra-low pressure measurement scale in vacuum technology. By definition, one micron equals one thousandth of a millimeter of mercury column absolute at zero degrees. This pre...

Q3. Vapor actuated pressure spring thermometers bypass the need for ambient temperature compensation, whereas gas or liquid expansion versions achieve compensation via__________________?

Select your answer for: Vapor actuated pressure spring thermometers bypass the need for ambient temperature compensation, whereas gas or liquid expansion versions achieve compensation via__________________?
Show answer

Answer: D. All A , B & C.

Filled thermal systems compensate for ambient temperature errors by maximizing bulb volume while minimizing capillary and receiving volumes. Larger bulb volumes ensure that temperature-induced fluid expansion is dominate...

Q4. What is the Laplace transform of an impulse input of magnitude „X‟?

Select your answer for: What is the Laplace transform of an impulse input of magnitude „X‟?
Show answer

Answer: D. 1

The Laplace transform of an ideal Dirac delta impulse function with magnitude X evaluates directly to X. Integrating the impulse function multiplied by the exponential kernel isolates the magnitude scaling factor cleanly...

Q5. Thermocouples are appropriate for measuring_________________?

Select your answer for: Thermocouples are appropriate for measuring_________________?
Show answer

Answer: D. Both high and low temperatures

Thermocouples generate thermoelectric voltages across wide temperature ranges based on the Seebeck effect. Different metal combinations allow thermocouples to measure cryogenic lows and extreme industrial highs. This bro...

Q6. Turbine flow meters are well-suited for_________________?

Select your answer for: Turbine flow meters are well-suited for_________________?
Show answer

Answer: D. Both B. and C.

Turbine flow meters provide high measurement accuracy and reliability, making them ideal for aerospace and cryogenic applications. Their compact mechanical design withstands extreme operating conditions while maintaining...